TYPE
|
Portable transformer winding resistance meter
|
PHYSICAL SPECIFICATIONS
|
Dimensions: 17.5”W x 11.75”H x 12.5”D (44.5 cm x 29.8 cm x 31.8 cm)
Weight: 27 lbs (12.2 kg)
|
INPUT POWER
|
100 – 120 Vac or 200 – 240 Vac (factory pre-set), 50/60 Hz
|
RESISTANCE READING RANGE
|
1 micro-ohm – 2,000 ohms
|
ACCURACY
|
1 – 19,999 micro-ohms: ±0.5% reading, ±1 count;
20 – 999 milli-ohms: ±1% reading, ±1 count;
1 – 2,000 ohms: ±1.5% reading, ±1 count
|
TEST VOLTAGE
|
36 Vdc max
|
TEST CURRENT RANGE
|
Auto range, 10 Amperes max
|
DISPLAY
|
5" back-lit LCD screen (240 x 128 pixels) viewable in bright sunlight and low-light levels
|
PRINTER
|
2.5-inch wide built-in thermal printer
|
KEYPAD
|
Rugged "QWERTY"-style membrane keypad
|
INTERNAL TEST RECORD STORAGE
|
Stores 100 test records of 64 readings each
|
COMPUTER INTERFACES
|
USB PC, USB Flash drive
|
PC SOFTWARE
|
Windows?-based software is included with purchase price
|
SAFETY
|
Designed to meet IEC61010 (1995), UL61010A-1, CSA-C22.2 standards
|
TEMPERATURE
|
Operating: -10?C to 50? C (15?F to +122? F)
Storage: -30? C to 70? C (-22?F to +158? F)
|
HUMIDITY
|
90% RH @ 40°C (104°F), non-condensing
|
ALTITUDE
|
2,000 m (6,562 ft) to full safety specifications
|
CABLES
|
Three 50-foot (15.24m) test cables, one ground cable, one power cord, one USB cable and cable carrying bag
|
OPTIONS
|
Shipping Case
|
WARRANTY
|
One year on parts and labor
|
Specifications are valid at nominal voltage and ambient temperature of +25?C (+77?F).
|