TYPE
|
Load tap changer analyzer
|
PHYSICAL SPECIFICATIONS
|
21”W x 17”H x 9” D (53 cm x 43 cm x 24 cm); Weight: 33 lbs (15.4 kg)
|
OPERATING VOLTAGE
|
100 – 240 Vac, 50/60 Hz
|
RESISTANCE READING RANGE
|
1 micro-ohm – 500 ohms
|
ACCURACY
|
1 – 19,999 micro-ohms: ±0.5% reading, ±1 count;
20 – 999 milli-ohms: ±1% reading, ±1 count;
1 – 500 ohms: ±1.5% reading, ±1 count
|
RESISTANCE CHANNELS
|
Three static resistance reading channels, One dynamic resistance channel
|
TEST VOLTAGE
|
60 Vdc max
|
TEST CURRENTS
|
1 ampere, 5 amperes, 10 amperes
|
AC CURRENT INPUT
|
Clamp-on current sensor, 1 – 20 Amperes
|
DISPLAY
|
Back-lit LCD Screen (64 x 128 dot graphic ); viewable in bright sunlight and low-light levels
|
PRINTER
|
4.5-inch wide thermal printer
|
EXTERNAL DATA STORAGE
|
One USB Flash drive interface port; stores up to 999 test records on a USB Flash drive (not included)
|
COMPUTER INTERFACES
|
One RS-232C port, One USB port
|
INTERNAL TEST RECORD STORAGE
|
Stores up to 128 static resistance test records (48 tests per record) and 11 dynamic resistance test records
|
LOAD TAP CHANGER CONTACT
|
240 Vac, 1A
|
SAFETY
|
Designed to meet UL 61010A-1 and CAN/CSA C22.2 No. 1010.1-92 standards
|
ENVIRONMENT
|
Operating: -10?C to 50? C (15?F to +122? F); Storage: -30? C to 70? C (-22?F to +158? F)
|
CABLES
|
One 50-foot current cable set, Three 50-foot resistance cable sets, One ground cable, One USB cable, One RS-232C cable, One LTC cable, power cord, cable bag
|
OPTIONS
|
Transportation Case
|
WARRANTY
|
One year on parts and labor
|
Specifications are valid at nominal voltage and ambient temperature of +25?C (+77?F).
|