The CBCT is a variable voltage DC power supply designed specifically to test substation circuit-breaker Open and Close coils. The CBCT uses the substation’s DC power supply to electronically generate a programmable output voltage from 5% to 95% of the source voltage. The CBCT can maintain up to an 80A test current while maintaining 2% or better voltage regulation during the circuit breaker coil operation.
-
One continuous and one pulse DC output
-
Back-lit LCD screen (20 characters by 4 lines)
-
Output voltage programmable from 5% to 95% of the input voltage
-
Built-in, single channel timer
CBCT
|
Technical Specifications
|
|
|
|
|
|
|
TYPE
|
Programmable DC Power Supply
|
PHYSICAL SPECIFICATIONS
|
19”W x 7”H x 15”D, (48 cm x 17 cm x 38 cm); Weight: 25 lbs (11.3 kg)
|
INPUT VOLTAGE
|
20 – 300 Vdc, 20A fuse
|
OUTPUT VOLTAGE
|
5% – 95% of input voltage with 2% regulation at max current (up to 80A)
|
OUTPUT VOLTAGE CHANNELS
|
One continuous and one pulse DC output
|
OUTPUT VOLTAGE PROTECTION
|
Shutdown if current exceeds 80A or if current drawing time exceeds 500 ms @ 80A
|
VOLT METER RANGE
|
Input/output meters, 0 – 300 Vdc; Accuracy: 1% of reading, ±0.2V
|
TIMER DISPLAY RANGE
|
0.0000 – 999.999 seconds; Accuracy: 0.01%, ±0.5 ms
|
TIMER START INPUT
|
Internal (coil initiation), wet-contact input (20 – 240 Vac/dc), or dry-contact input (1 – 200 ohms)
|
TIMER STOP INPUT
|
Wet-contact (20 – 240 Vac/dc) or dry-contact (1 – 200 ohms)
|
DISPLAY
|
Back-lit LCD screen (20 characters by 4 lines); viewable in both bright sunlight and low-light levels
|
SAFETY
|
Designed to meet UL 6101A-1 and CAN/CSA C22.2 No 1010.1-92 standards
|
ENVIRONMENT
|
Operating: -10°C to 50°C (+15°F to +122°F); Storage: -30°C to70°C (-22°F to +158°F)
|
CABLES
|
Two 6-foot (#8 AWG) DC cable sets, Two 10-foot timer cable sets, One ground cable, one cable bag
|
OPTIONS
|
Transportation case
|
WARRANTY
|
One year on parts and labor
|
Specifications are valid at nominal voltage and ambient temperature of +25?C (+77?F).
|
|